Specification |
Model HDSX-T | 4KVA | 6KVA | 7KVA | 8KVA |
Rated Power | 3.2KW | 4.8KW | 5.6KW | 6.4KW |
Peak Power(20ms) | 9.6KW | 14.4KW | 16.8KW | 19.2KW |
Starter Motor | 3HP | 4HP | 4HP | 4HP |
Battery Voltage | 48/96/192VDC |
Size(L*W*Hmm) | 565*300*775 |
Packing Size(L*W*Hmm) | 625*360*895 |
N.W.(kg) | 58 | 73 | 75 | 80 |
G.W.(kg)(Carton Packing) | 71 | 86 | 88 | 93 |
Installation Method | Tower |
Parameter |
Input | DC Input Voltage Range | 10.5VDC-15VDC(Single battery voltage) |
AC Input Voltage Range | 380Vac/400Vac±10%(customized 190Vac/200Vac) |
AC Input Frequency Range | 45Hz-65Hz |
Max AC charging current | 20A/10A/5A | 20A/10A/5A | 20A/10A/5A | 25A/15A/10A |
AC charging method | Three-stage (constant current, constant voltage, floating charge) |
Phase | 3/N/PE |
Output | Efficiency(Battery Mode) | ≥85% |
Output Voltage(Battery Mode) | 380Vac/400Vac±10%(customized 190Vac/200Vac) |
Output Frequency(Battery Mode) | 50/60Hz ±1% |
Output Wave(Battery Mode) | Pure Sine Wave |
Output waveform distortion | Linear load≤3% |
Efficiency(AC Mode) | >99% |
Output Voltage(AC Mode) | Conforming to AC input |
Output Frequency(AC Mode) | Conforming to AC input |
No load loss(Battery Mode) | ≤1% rated power |
No load loss(AC Mode) | ≤2% rated power( charger does not work in AC mode) |
No load loss(Energy saving Mode) | ≤10W |
Phase | 3/N/PE |
Battery type (Optional) | U0: Gel U.S.A | Charge Voltage:14V;Float Voltage:13.7V(Single battery voltage) |
U1: A.G.M.1 | Charge Voltage:14.1V;Float Voltage:13.4V(Single battery voltage) |
U2: A.G.M.2 | Charge Voltage:14.6V;Float Voltage:13.7V(Single battery voltage) |
U3: Sealed lead Acid | Charge Voltage:14.4V;Float Voltage:13.6V(Single battery voltage) |
U4: Gel European | Charge Voltage:14.4V;Float Voltage:13.8V(Single battery voltage) |
U5: Open lead Acid | Charge Voltage:14.8V;Float Voltage:13.5V(Single battery voltage) |
U6: Calcuim(open) | Charge Voltage:15.1V;Float Voltage:13.6V(Single battery voltage) |
U7: Sulphation cycle | 15.5V for 4hrs |
customize battery | Charge and discharge parameters of different types of batteries (such as lithium batteries, etc.) can be customized according to user requirements. |
Protection | Battery undervoltage alarm | 11V(Single battery voltage) |
Battery undervoltage protection | 10.5V(Single battery voltage) |
Battery overvoltage alarm | 15V(Single battery voltage) |
Battery overvoltage protection | 17V(Single battery voltage) |
Battery overvoltage recovery voltage | 14.5V(Single battery voltage) |
Overload power protection | Automatic protection (battery mode), circuit breaker or insurance (AC mode) |
Output short circuit protection | Automatic protection (battery mode), circuit breaker or insurance (AC mode) |
Temperature protection | >90°C(Shut down output) |
Alarm | A | Normal working condition, buzzer has no alarm sound |
B | Buzzer sounds 4 times per second when battery failure, voltage abnormality, overload protection |
C | When the machine is turned on for the first time, the buzzer will prompt 5 when the machine is normal |
Inside Solar controller | Charging Mode | MPPT or PWM |
Charging current | 48V System:10A,20A,30A,40A,50A,60A; 96V/192V System:50A,100A,150A,200A |
PV Input Voltage Range | 48V System:60V-88V;96V System:120V-176V;192V System:240V-352V |
Max PV Input Voltage(At 25℃) | 48V System:100V;96V System:200V;192V System:400V |
PV Array Maximum Power | 48V System:560W,1120W,1680W,2240W,2800W,3360W; 96V System:5.6KW,11.2KW,8.4KW*2,11.2KW*2 192V System:11.2KW,22.4KW,16.8KW*2,22.4KW*2 |
Standby loss | ≤3W |
Maximum conversion efficiency | >95% |
Working Mode | Battery First/AC First/Saving Energy Mode |
Transfer Time | ≤4ms |
Display | LCD |
Thermal method | Cooling fan in intelligent control |
Communication | RS232/RS485/APP/SNMP/GSM (Optional) |
Environment | Operating temperature | -10℃~40℃ |
Storage temperature | -15℃~60℃ |
Noise | 2000m(More than derating) |
Elevation | ≤65dB |
Humidity | 0%~95% ,No condensation |
Warranty | 3 years |
Note: All specifications are subject to change without prior notice |